6AG1332-5HD01-7AB0 – SIEMENS

Stokta

SIPLUS S7-300 SM 332 4AQ U/I based on 6ES7332-5HD01-0AB0 with conformal
coating, -25…+70 °C, analog output SM 332, isolated, 4 AQ, U/I; diagnostics;
resolution 11/12 bits, 20-pole, removing and inserting possible with active
backplane bus

Açıklama

WARNING: For see product specifications click “SPECIFICATIONS”.
UYARI: Ürün özelliklerini görmek için “SPECITIFATIONS”a tıklayınız.

6AG1332-5HD01-7AB0 – SIEMENS

SIPLUS S7-300 SM 332 4AQ U/I based on 6ES7332-5HD01-0AB0 with conformal
coating, -25…+70 °C, analog output SM 332, isolated, 4 AQ, U/I; diagnostics;
resolution 11/12 bits, 20-pole, removing and inserting possible with active
backplane bus

 

6AG1332-5HD01-7AB0 - SIEMENS

General information
based on 6ES7332-5HD01-0AB0
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 240 mA
from backplane bus 5 V DC, max. 60 mA
Power loss
Power loss, typ. 3 W
Analog outputs
Number of analog outputs 4
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
● 0 to 10 V Yes
● 1 V to 5 V Yes
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 1 µF
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 10 mH
Cable length
● shielded, max. 200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0
mA to 20 mA: 12 bit
● Conversion time (per channel) 0.8 ms
Settling time
● for resistive load 0.2 ms
● for capacitive load 3.3 ms

● for inductive load 0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH)
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-) 0.5 %; ±0.6 % @ < 0 °C or > 60 °C
● Current, relative to output range, (+/-) 0.6 %; ±0.7 % @ < 0 °C or > 60 °C
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-) 0.4 %
● Current, relative to output range, (+/-) 0.5 %
Interrupts/diagnostics/status information
Diagnostics function Yes; Parameterizable
Alarms
● Diagnostic alarm Yes; Parameterizable
Diagnoses
● Diagnostic information readable Yes
Diagnostics indication LED
● Group error SF (red) Yes
Potential separation
Potential separation analog outputs
● between the channels No
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
● between the channels and the power supply of the
electronics
Yes
Isolation
Isolation tested with 500 V DC
Standards, approvals, certificates
CE mark Yes
UL approval Yes; File E239877
RCM (formerly C-TICK) Yes
KC approval Yes
EAC (formerly Gost-R) Yes
Railway application
● EN 50121-4 No
● EN 50155 No
Ambient conditions
Ambient temperature during operation
● min. -25 °C; = Tmin
● max. 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m
● Ambient air temperature-barometric pressure-altitude Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax
- 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K)
at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-
2-38, max.
100 %; RH incl. condensation/frost (no commissioning under condensation
conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN
60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna);
Class 3B3 on request
— to chemically active substances according to EN
60721-3-3
Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity
degree 3); *
— to mechanically active substances according to EN
60721-3-3
Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN
60721-3-6
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on
request
— to chemically active substances according to EN
60721-3-6
Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity
degree 3); *
— to mechanically active substances according to EN Yes; Class 6S3 incl. sand, dust; *

60721-3-6
Usage in industrial process technology
— Against chemically active substances acc. to EN
60654-4
Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring
and control systems acc. to ANSI/ISA-71.04
Yes; Level GX group A/B (excluding trichlorethylene; harmful gas
concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level
LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental
conditions acc. to EN 60721, EN 60654-4 and
ANSI/ISA-71.04
* The supplied plug covers must remain in place over the unused interfaces
during operation!
connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 220 g